In electrical engineering, single-phase
electric power refers to the distribution of alternating current electric power using a system in which all the voltages of the supply vary
in unison. Single-phase distribution is used when loads are mostly lighting and
heating, with few large electric motors. A single-phase supply connected to an
alternating current electric motor does not produce a revolving magnetic field; single-phase
motors need additional circuits for starting, and such motors are uncommon
above 10 or 20 kW in rating.
In contrast, in a three-phase system, the currents in each
conductor reach their peak instantaneous values sequentially, not
simultaneously; in each cycle of the power frequency, first one, then the
second, then the third current reaches its maximum value. The waveforms of the
three supply conductors are offset from one another in time (delayed in phase) by one-third of their period.
Standard frequencies of single-phase power systems are either 50 or 60 Hz. Special single-phase traction power networks may operate at 16.67 Hz or other
frequencies to power electric railways.
Splitting
out
Single phase polemount Canadian
stepdown transformer.
No arrangement of transformers can convert a single-phase load
into a balanced load on a polyphase system. A single-phase load may be powered
from a three-phase distribution system either by connection between a phase
and neutral or by connecting the load between
two phases. The load device must be designed for the voltage in each case. The
neutral point in a three phase system exists at the mathematical center of an
equilateral triangle formed by the three phase points, and the phase-to-phase
voltage is accordingly
times the phase-to-neutral voltage.[1] For example, in places using a 415 volt 3 phase system, the
phase-to-neutral voltage is 240 volts, allowing single-phase lighting to be
connected phase-to-neutral and three-phase motors to be connected to all three
phases.
In North America, a typical
three-phase system will have 208 volts between the phases and 120 volts between
phase and neutral. If heating equipment designed for the 240-volt three-wire single phase system is connected to two phases
of a 208 volt supply, it will only produce 75% of its rated heating effect. Single-phase
motors may have taps to allow their use on either 208 V or 240 V supplies.
On higher voltage systems
(kilovolts) where a single phase transformer is in use to supply a low voltage
system the method of splitting varies. In North America utility distribution
practice, the primary of the step-down transformer is wired across a single high voltage feed wire and
neutral, at least for smaller supplies (see photo of transformer on right). Rural distribution may be a single phase at a medium voltage; in
some areas single
wire earth return
distribution is used when customers are very far apart. In Britain the
step-down primary is wired phase-phase.
Single-phase power distribution is
widely used especially in rural areas, where the cost of a three-phase
distribution network is high and motor loads are small and uncommon.
High power systems, say, hundreds of
kVA or larger, are nearly always three phase. The largest
supply normally available as single phase varies according to the standards of
the electrical utility. In the UK a single-phase household supply may be rated
100A or even 125A, meaning that there is little need for 3 phase in a domestic
or small commercial environment. Much of the rest of Europe has traditionally
had much smaller limits on the size of single phase supplies resulting in even
houses being supplied with 3 phase (in urban areas with three-phase supply
networks).
In North America, individual
residences and small commercial buildings with services up to about 100 kV·A
(417 amperes at 240 volts) will usually have three-wire single-phase distribution, often with only one
customer per distribution transformer. In exceptional cases larger single-phase
three-wire services can be provided, usually only in remote areas where
polyphase distribution is not available. In rural areas farmers who wish to use
three-phase motors may install a phase converter if only a single-phase supply is
available. Larger consumers such as large buildings, shopping centres,
factories, office blocks, and multiple-unit apartment blocks will have
three-phase service. In densely-populated areas of cities, network power
distribution is used with many customers and many supply transformers connected
to provide hundreds or thousands of kV·A load concentrated over a few hundred
square metres.
Three-wire single-phase systems are
rarely used in the UK where large loads are needed off only two high voltage
phases.
Single-phase power may be used for electric railways; the largest single-phase generator in the world, at Neckarwestheim Nuclear Power Plant, supplies a railway system on a
dedicated traction power network.
Typically a third conductor, called ground (or "safety ground")
(U.S.) or protective earth (Europe, IEC), is used as a protection
against electric shock, and ordinarily only carries significant current when there
is a circuit fault. Several different earthing systems are in use.
- ^ See three phase. This arises from the phase difference between the conductors. If two conductors are energized with ac voltages that are the same magnitude and in-phase, there will be no voltage difference between them. If the voltages are the same magnitude and one voltage is delayed one-half cycle with respect to the other, the voltage between the two will be double. In a three phase system the phase difference between conductors is one-third of a cycle; a little bit of algebra would show that the voltage difference between two conductors is the square root of three the magnitude of the phase to neutral voltage.